For the indication of the 4 to 20 mA signal or the HART® values in the field or in the panel!
Field of application
The process indicator is available with 4 to 20 mA or with HART® protocol. In the HART® version up to 4 measured values of one sensor can be indicated in alternation. For this the indicator can be set as primary or secondary HART® master and actively inquire the values from the sensor. The small voltage drop of < 1V (< 1.9 V with HART®) is a huge advantage especially in Ex-applications, where in most cases only a reduced voltage is available.
Display of 4 to 20 mA measured values or HART® process variables in all industries
Panel-mount housing or field housing as local display
Scalable display value
With the "Level" or "Analysis" options, basic settings can be made on selected sensors and available measured values and units can be preset quickly and easily.
Benefits
Display of 4 to 20 mA measured values or optionally up to four of a sensor's HART® process variables in all industries; Use as primary or secondary HART® master
5-digit measured value display with 17 mm (0.67") character height with dimension and bargraph; backlight can be activated
Panel-mount housing (IP65) or field housing (IP66; Ex approval) as local display; Minimal installation depth
No external power supply required; Voltage drop ≤1 V (HART® ≤1.9 V)
Easy 3-key operation for configuring the device
International approvals; marine approval
SIL interference freeness acc. to EN 60508
Specifications
Measuring principle
Loop powered indicators
Measuring principle
Loop-powered field indicator
Function
Display
Display
LCD 17 mm (0.67") 5-digit 7-segment bargraph Plain text display for unit/TAG Activatable backlight
Power Supply
Loop powered
Input
1 x analogue 4...20 mA/HART®
Output
Not defined
Software functions
Not defined
Certificates
ATEX II2(1)G Ex ib [ia Ga] IIC T6 Gb CSA C/US IS CI.I Div.1 Gr.A-D CSA C/US NI CI.I Div.2 Gr.A-D CSA Ex ia, CI. I, Div. 1, Gr. ABCD FM IS, CI. I, Div. 1, Gr. ABCD EAC 1Ex ib IIC T6 Gb IECEx Ex ib [ia Ga] IIC T6 Gb JPN Ex ib IIC Gb NEPSI Ex ib IIC Gb UK II2(1)G Ex ib [ia Ga] IIC T6 Gb ATEX IECEx II2(1)G Ex ib [ia Ga] IIC T6 marine certificate UL C/US
SIL
Not defined
Panel mounting
field panel mounting