One or two-channel barrier for the safe separation of 4...20 mA standard signal circuits
Field of applicationThe RB223 passive barrier can be used to galvanically isolate active signal circuits (0 to 20 mA) in three applications:Transmission from non-Ex to Ex areas e.g for active adjusters, controllers or indicators,Transmission from Ex to non-Ex areas for connection of active, intrinsically safe circuits to the PLC,Transmission from Ex to non-Ex areas for supply of intrinsically safe transmitters with non-intrinsically safe transmitter power supply. Separation of active 0/4 to 20 mA signals from transmitters, valves and adjusters. | Benefits
|
Specifications
| Measuring principle | Passive barrier |
| Measuring principle | Power supply |
| Function | Passive barrier for safe seperation of 4...20 mA current circuit |
| Loop power supply | Loop powered |
| Auxiliary power supply / Loop power supply | Loop powered |
| Input | 2 x analog 4...20 mA |
| Output | 2 x analog 4...20 mA |
| Certificates | ATEX II(1)GD(Ex ia)IIC |
| Operation | HART |